6 detector status, Detector status, Table 7: detector status – Spectrex 40/40U-UB - UV Flame Detector User Manual

Page 25: Table 8: output signals versus detector state

background image

TM 40/40U, Rev (7) July 2013

Performance Considerations

13

1.5.6 Detector Status

The possible detector function statuses are listed in Table 7. A more detailed
fault analysis can be seen via HART or RS485.

Table 7: Detector Status

Status

Description

Normal

Normal operation.

BIT

Built-In-Test being performed.

Warning

Fire detected - changed to Warning (pre-alarm state).

Alarm

Fire detected - changed to Fire Alarm state.

Latched Alarm
(Optional)

The alarm outputs remain latched on following detection
of a fire that has already been extinguished.

BIT Fault

A fault is detected during BIT sequence or other electric
failure. The detector will continue to detect for fire.

Fault

A fault is detected when the power supply is too low or
due to a software fault or electrical failure. The detector
will NOT detect fire in this condition.

In each state, the detector activates different outputs, as specified in
Table 8.

Table 8: Output Signals versus Detector State

Detector
State

LED
Indicator

LED
Mode

Alarm
Relay

Auxiliary
Relay

Fault
Relay

mA
output

Normal

Green

1Hz

Off

Off

On

4 mA

Warning

Red

2Hz

Off

On

(4)

On

16 mA

Alarm

(1)

Red

Constant

On

On

On

20 mA

Latch

(2)

Red

Constant

On

Off

On

20 mA

On

(4)

On

20 mA

BIT Fault

(3)

Yellow

4Hz

Off

Off

Off

2 mA

Warning at
BIT Fault

Red

2Hz

Off

On

(4)

Off

16 mA

Alarm at
BIT Fault

Red

Constant

On

On

Off

20 mA

Fault

Yellow

4Hz

Off

Off

Off

0 mA

Notes:

1

The alarm outputs are activated while alarm conditions exist and will
stop approximately 5 seconds after the fire is no longer detected.

2

The Alarm state can be optionally latched via programmed function.
(Default is non-latching).