10
Performance Considerations
1.5.3 False Alarms Prevention
To prevent false alarms, the detector will not alarm or react to the radiation
sources specified in Table 4.
Table 4: Immunity to False Alarm Sources
Radiation Source
Immunity
Distance ft. (m)
Indirect or reflected sunlight
IAD
Vehicle headlights (low beam) conforming to
MS53023-1
IAD
Incandescent frosted glass light, 300 W
IAD
Fluorescent light with white enamel reflector, standard
office or shop, 70 W (or two 35 W)
IAD
Electric arc [12mm (
15
/
32
") gap at 4000 V alternating
current, 60 Hz]
IAD
Ambient light extremes (darkness to bright light with
snow, water, rain, desert glare and fog)
IAD
Bright colored clothing, including red and safety
orange
IAD
Blue-green dome light conforming to M251073-1
IAD
Flashlight (MX 991/U)
IAD
Radiation heater, 3000 W
IAD
Radiation heater, 1000 W with fan
IAD
Lit cigar
5 (1.5)
Lit cigarette
5 (1.5)
Match, wood, stick including flare up
16.5 (5)
Notes:
IAD = Immune at Any Distance.