Technical Specifications
43
A
Specifications
➣ In this appendix…
page 43
page 44
page 44
page 46
page 46
page 47
A.1
Technical Specifications
Spectral Response
UV 0.185-0.260 µm
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
50 / 15
Kerosene
37 / 11
Gasoline
50 / 15
Ethanol 95%
37 / 11
Diesel Fuel
37 / 11
Methanol
37 / 11
JP5
37 / 11
IPA (Isopropyl
Alcohol)
37 / 11
Hydrogen*
33 / 10
Polypropylene
Pellets
18 / 5
Methane*
40 / 12
Silane*
22 / 7
Office Paper
20 / 6
LPG*
40 / 12
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 3 seconds
200 msec response to flash fire
Adjustable Time Delay Up to 30 seconds
Sensitivity Ranges
1 ft
2
(0.1m
2
) n-heptane pan fire from 50 ft. (15m)
Fields of View
Horizontal 100
, Vertical 95
Built-In-Test (BIT)
Automatic (and Manual)