beautypg.com

A specifications, Specifications, Technical specifications – Spectrex 40/40U-UB - UV Flame Detector User Manual

Page 55: Aspecifications, A.1 technical specifications

background image

Technical Specifications

43

A

Specifications

In this appendix…

Technical Specifications

page 43

Electrical Specifications

page 44

Outputs

page 44

Approvals

page 46

Mechanical Specifications

page 46

Environmental Specifications

page 47

A.1

Technical Specifications

Spectral Response

UV 0.185-0.260 µm

Detection Range

(at highest Sensitivity
Setting for 1ft

2

(0.1m

2

) pan

fire)

Fuel

ft. / m

Fuel

ft. / m

n-Heptane

50 / 15

Kerosene

37 / 11

Gasoline

50 / 15

Ethanol 95%

37 / 11

Diesel Fuel

37 / 11

Methanol

37 / 11

JP5

37 / 11

IPA (Isopropyl
Alcohol)

37 / 11

Hydrogen*

33 / 10

Polypropylene
Pellets

18 / 5

Methane*

40 / 12

Silane*

22 / 7

Office Paper

20 / 6

LPG*

40 / 12

* 20" (0.5m) high, 8" (0.2m) width plume fire

Response Time

Typically 3 seconds
200 msec response to flash fire

Adjustable Time Delay Up to 30 seconds

Sensitivity Ranges

1 ft

2

(0.1m

2

) n-heptane pan fire from 50 ft. (15m)

Fields of View

Horizontal 100

, Vertical 95

Built-In-Test (BIT)

Automatic (and Manual)