TM 40/40U, Rev (7) July 2013

Internal Detector Tests

17

1.6.2.3 Manual BIT

The BIT is manually initiated by momentarily connecting Terminal 3 with
Terminal 2 (or a switch across these terminals in the safe area).

The results of a successful and unsuccessful Manual BIT are listed in
Table 11 and Table 12.

Table 11: Results of a Successful Manual BIT

Output

Result

FAULT relay

Wiring options 1, 2, and 4: remains CLOSED (Normal)

Wiring options 3 and 5: remains OPEN (Normal)

ALARM relay

Activated for 3 sec (only when the function Alarm BIT is
set to YES)

AUXILIARY
relay

For wiring options 4 and 5: is activated for 3 sec (only
when the function Auxiliary BIT is set to YES)

0-20mA
output

Wiring option 1, 2, 3:

Initiates 20 mA only when the function Alarm BIT is set

to YES

Initiates 16 mA when the function Auxiliary BIT is set

to YES and the function Alarm BIT is set to NO

POWER LED

Green, Flashing, 1 Hz

Table 12: Results of an Unsuccessful Manual BIT

Output

Result

FAULT relay

Wiring option 1, 2, 4: changes to OPEN

Wiring option 3 and 5:changes to CLOSED

0-20mA
output

Wiring option 1, 2, 3: Indicates BIT FAULT (2mA)

POWER LED

Yellow, Flashing, 4 Hz

1.6.2.4 Manual BIT only selected

The BIT is initiated manually by momentarily connecting Terminal Number 3
with Terminal Number 2 or a switch across these terminals in the safe area.