Internal Detector Tests

1.6.2.2 Automatic BIT

The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.

All outputs of BIT results will function as described in Table 9 and Table 10,
and the BIT will be automatically executed every 1 minute.

This continues until a successful BIT occurs, when the detector resumes
normal operation.

Table 9: Results of a Successful BIT

Output

Result

Fault relay

Wiring options 1, 2, 4: remains CLOSED

Wiring options 3 and 5: remains OPEN

0-20mA
output

Wiring option 1, 2, 3: Normal (4 mA)

Power LED

Green, Flashing, 1 Hz On (Normal)

Table 10: Results of an Unsuccessful BIT

Output

Result

Fault relay

Wiring option 1, 2, 4: changes to Open

Wiring option 3 and 5: changes to Closed

0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED

Yellow, Flashing, 4 Hz

BIT procedure

Performed every 1 minute