Connecting the Detector

2.7.1 Verifying the Detector Wiring

The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.

Table 14 describes the function of each terminal for all the wiring options.

Table 14: Model 40/40U and UB Wiring Options

Wire
Terminal
No.

Option 1
Default

Option 2

Option 3

Option 4

Option 5

1

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

2

0 VDC

0 VDC

0 VDC

0 VDC

0 VDC

3

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

4

Fault

Relay N.C.

Fault

Relay N.C.

Fault

Relay N.O.

Fault

Relay N.C.

Fault

Relay N.O.

5

6

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

7

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

8

0-20mA

In

Alarm

Relay N.C.

Alarm

Relay N.C.

Auxiliary

N.O.

Auxiliary

N.O.

9

0-20mA

Out

0-20mA

Out*

0-20mA

Out*

Auxiliary

C

Auxiliary C

10

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

11

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

12

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

*Available with the HART protocol.

Notes:

RS-485 is used for communication network as specified in Appendix C
(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.

Alarm relay:

N.O. energized contact in wiring options 1, 4, 5.

N.O. and N.C. energized in options 2 and 3.

0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.

0-20mA 'Source' in options 2 and 3 available with the HART protocol.

In Wiring Option 1, link Terminals 1 and 8 to change the mA output to
‘Source’.