3 other fuels, Table 3: fuel sensitivity ranges – Spectrex 40/40U-UB - UV Flame Detector User Manual
Page 20
SharpEye
TM
UV Flame Detector User Guide
8
Performance Considerations
Note: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, and so on.
1.5.1.3 Other Fuels
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1ft
2
(0.1m
2
) and is defined as
100% sensitivity.
For fuel fire – standard pan fire size: 1 ft
2
(0.1 m
2
).
For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.
Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Type Of Fuel
Max. Distance (ft./m)
40/40U and UB
Gasoline
50/15
N-Heptane
50/15
JP5
37/11
Kerosene
37/11
Diesel Fuel
37/11
Ethanol 95%
37/11
IPA
37/11
Methanol
37/11
Methane
40/12
LPG
40/12
Paper
20/6
Polypropylene
18/5
Hydrogen
33/10
Silane
22/7