beautypg.com

3 other fuels, Table 3: fuel sensitivity ranges – Spectrex 40/40U-UB - UV Flame Detector User Manual

Page 20

background image

SharpEye

TM

UV Flame Detector User Guide

8

Performance Considerations

Note: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, and so on.

1.5.1.3 Other Fuels

The detector reacts to other types of fire as follows:

The baseline fire refers to n-heptane 1ft

2

(0.1m

2

) and is defined as

100% sensitivity.

For fuel fire – standard pan fire size: 1 ft

2

(0.1 m

2

).

For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.

Maximum Response Time: 10 sec.

Table 3: Fuel Sensitivity Ranges

Type Of Fuel

Max. Distance (ft./m)

40/40U and UB

Gasoline

50/15

N-Heptane

50/15

JP5

37/11

Kerosene

37/11

Diesel Fuel

37/11

Ethanol 95%

37/11

IPA

37/11

Methanol

37/11

Methane

40/12

LPG

40/12

Paper

20/6

Polypropylene

18/5

Hydrogen

33/10

Silane

22/7