beautypg.com

2 built-in-test (bit), 1 how the bit operates, Built-in-test (bit) – Spectrex 40/40U-UB - UV Flame Detector User Manual

Page 27

background image

TM 40/40U, Rev (7) July 2013

Internal Detector Tests

15

Relays and heater operation

Processor Watch dog

Software

Memory

Oscillator frequency

Response to Fault Indication

If a failure is found, the detector indicates by:

Fault relay:

Opens in wiring option 1, 2, and 4

Closes in wiring option 3 and 5

0-20mA: indicates Fault (0mA or 2mA) in wiring option 1, 2, 3

LED – Yellow flashes (4 Hz)

Correcting the Fault

The fault indications remain until the detector’s power is removed. The fault
indications return if the fault is still found when power is restored.

1.6.2 Built-In-Test (BIT)

The detector’s Built-In-Test (BIT) also checks the following:

Electronics circuitry

Sensors

Window cleanliness

The detector can be set to perform the BIT in the following modes:

Automatically and manually

Manually only

Note: In Manual BIT, the outputs may also be tested and Control System
‘inhibit’ should be applied if this could initiate other systems.

1.6.2.1 How the BIT Operates

The detector's status remains unchanged if the result of a BIT is the
same as the current status (NORMAL or BIT Fault)

the detectors’ status is changed (from Normal to BIT Fault or vice versa)
if the BIT differs from the current status

Note: In ‘BIT Fault’ status the detector can continue to detect a fire.