Table 22: electromagnetic compatibility (emc) – Spectrex 40/40U-UB - UV Flame Detector User Manual
Page 60
SharpEye
TM
UV Flame Detector User Guide
48
Environmental Specifications
Vibration
Designed to meet MIL-STD-810C, method
514.2, procedure VIII
Vibration at an acceleration of 1.1g within the
frequency range of 5-30 Hz, and an
acceleration of 3g within the frequency range
of 30-500 Hz
Mechanical Shock
Designed to meet MIL-STD-810C, method
516.2, procedure I
Mechanical Shock of 30g half-sine wave, for
11 msec
Electromagnetic
Compatibility (EMC)
See Table 22
Table 22: Electromagnetic Compatibility (EMC)
Test Standard
Level Per
Electrostatic Discharge ESD
IEC 61000-4-2
IEC 61326-3
Radiated EM Field
IEC 61000-4-3
IEC 61326-3
Electrical Fast Transients
IEC 61000-4-4
IEC 61326-3
Surge
IEC 61000-4-5
IEC 61326-3
Conducted Disturbances
IEC 61000-4-6
IEC 61326-3
Power Ferq. Magnetic Field
IEC 61000-4-8
IEC 61326-3
Radiated Emission
IEC 61000-6-3
EN 55022
Conducted Emission
IEC 61000-6-3
EN 55022
Immunity to Main Supply
Voltage Variations
MIL-STD-1275B
To fully comply with EMC directive and protect against interference caused
by RFI and EMI, the cable to the detector must be shielded and the detector
must be grounded. The shield should be grounded at the detector end.