KYORITSU 4106 User Manual

Page 12

background image

8

● Measuring method for Earth Resistance

  Fall-of-potential method (currents and voltages measured via the Probes)

● Measurement method of Earth Resistivity (ρ)

  Wenner 4-pole method

● Output Characteristics

  Measuring Voltage Um (max.) approx 10Vrms 94Hz, 105Hz, 111Hz,

128Hz

  Measuring Current Im

(max.) approx 80mA, however, Im ×(Re+Rh)

< Um

● Measuring Method for Series Interference Voltage (earth voltage)

  RMS Rectifier (between the E-S Terminals)

● Memory Capacity : 800 data

● Communication Interface : Model 8212USB Optical Adaptor

● LCD Dot-matrix 192×64, monochrome

Backlight

Earth resistance

: max 209.9kΩ

Earth resistivity

: 1999kΩ・m

Series Interference Voltage : max 50.9V

● Low Battery Warning

: Battery mark appears.

● Continuous Measurement : 400 times or more with manganese batteries;

repeating measurements at every 30 sec

with a load of 1Ω at 2Ω Range.

● Over-range Indication

: “OL”

● Auto-Power-Off

: automatically powered off when 5 min

passes without any Key operation.

● Location for use

: Indoor/ Outdoor use (Not completely waterproof),

altitude 2000m or less

● Applicable range

: Testing earth resistance on power distribution

lines, in-house wiring system and electrical

appliances

● Temperature & Humidity range (guaranteed accuracy) :

  23℃±5℃ , relative humidity 85% or less (no condensation)

● Operating Temperature & Humidity range :

  -10℃ ~ 50℃ , relative humidity 75% or less (no condensation)

* Supplied Test leads cannot be used at 0ºC or less.

● Storage Temperature & Humidity range :

  -20℃ ~60℃ , relative humidity 75% or less (no condensation)

● Overload Protection : between E-S(P) and between E-H(C) terminals

  AC280V / 10 sec

● Withstand Voltage

: between the electrical circuit and enclosure

AC3540V(50/60Hz) / 5 sec

● Insulation Resistance

: between the electrical circuit and enclosure

50MΩ or more / DC1000V