Technical data

4.1 Technical

data

Application

Range of applications

Continuous level measurement of liquids, solids and powders

Function and system design
Measuring principle

Time domain reflectometry using a direct mode of measurement

Equipment architecture

See section 4.2

Input

Measured variable

Distance (between the reference point – gauge flange facing –
and the product surface), level, liquid interface & volume

Measurement range

Variable according to probe type, see Equipment architecture,
section 4.2.1 Minimum tank height = 0.15 m or 0.5 ft.

Blocking Distance
(dead zone)

Variable according to probe type, see probe measurement limits,
section 4.2.2

Output

Analogue

4 … 20 mA, passive output

Load

Passive outputs

750 Ω maximum

Error signal

22 mA

Resolution

± 3 µA

Digital HART

®

, passive output

Digital, Ex ia

HART

®

, passive intrinsically-safe output

Signal on alarm

Status markers via PC STAR 2 or HART

®

controller (HHC)

Performance characteristics
Reference operating conditions
Ambient temperature

+20°C ± 5°C or +68°F ± 9°F

Ambient air pressure

1013 mbar abs. ± 20 mbar or 14.69 psig ± 0.29 psi

Relative air humidity

60% ± 15%

Reference target

- coaxial probe :

water surface

- single probe :

Ø 0.8 m or Ø 31.5 in. metal plate

- twin probe :

metal block “short circuit”

Free space diameter

> 300 mm or > 11.81” *

Distance to obstruction

> 1 m or > 3.3 ft.

Accuracy

Level measurement

Liquids when probe length, L ≤ 15 m or 50 ft.

± 15 mm or 0.6” outside the dead zone
Optional: ± 5 mm or 0.2”

Liquids when probe length, L > 15 m or 50 ft.

± 15 mm or 0.6” ± 0.1% of the measured distance
Optional: ± 0.05% of the measured distance

Solids

(powders)

± 20 mm or 0.8”

with 4 … 20 mA current output

± 0.01% of the measured distance


* not for coaxial probe.