background image

4

ELECTRICAL CONNECTIONS

28

TIDALFLUX 2300 F

www.krohne.com

06/2013 - 4002490202 MA TIDALFLUX 2300 F R02 en

4.9 Interface cable

The data interface cable is a shielded, 3 x 1.5 mm

2

LIYCY cable.

1 Strip the conductor to dimension a.
2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Crimp the wire end ferrules onto the conductors 1, 2 and 3.

Connect the shielding at both sides of the cable via the special cable gland.

Preparing the interface cable

Figure 4-16: Preparing the interface cable

a = 100 mm / 4"
b = 10 mm / 0.4"