Electrical connections, 6 connection box ifc 300 f / pf – KROHNE TIDALFLUX 2300 F EN User Manual

Page 23

background image

ELECTRICAL CONNECTIONS

4

23

TIDALFLUX 2300 F

www.krohne.com

06/2013 - 4002490202 MA TIDALFLUX 2300 F R02 en

Description of connections

4.3.6 Connection box IFC 300 F / PF

The connection box of the IFC 300 signal converter is especially made with an extra cable entry.

This cable entry is positioned on the right, just below the regular entries. The field current cable

has to be lead through this entry and must be connected on the contacts as described in the

figure below (see table "Description of connections" also).

Terminals

Terminals

Terminals

Terminals

Function, electrical data

Function, electrical data

Function, electrical data

Function, electrical data

L, N

L+, L-

Connections for mains supply;

Type of protection Ex e,

100...230 VAC, +10%/-15%, 22 VA

12...24 VDC, +30%/-10% (short-time: -25%), 12 W

24 VAC, +10%/-15%, 22 VA

24 VDC, +30%/-25%, 12 W

U

m

= 253 V

A, A-, A+

B, B-

C, C-

D, D-

Connections for signal I/Os (PELV circuits);

Type of protection Ex e or Ex ia,

dependent on the specific version of the signal

converter ordered. Consult the tables with CG

numbers for details.

Figure 4-10: Electrical connections

1 turn cover counterclockwise
2 remove connection box cover
3 upper left/right & bottom right cable entries
4 connection field current and signal cable (depending on used cable BTS / DS 300)
5 bottom right cable connection (RS 485 circuit)
6 signal converter

Terminals

Terminals

Terminals

Terminals

Function, electrical data

Function, electrical data

Function, electrical data

Function, electrical data

7

8

9

Connections for field current cable

connection 9 = nc.

E

C

D

Connections for RS 485 circuit

Type of protection Ex e or Ex ia,

1

2 - 20

3 - 30

ground

Connections for signal cable

(Depending on used cable BTS / BS 300)