3.6.4 Mounting advice for difficult situations
If you can not meet the installation conditions install the flowmeter between two containers. The
inlet to the flowmeter must be higher than the outlet of the fluid. In this way you will have a calm
flow into the flowmeter, resulting in a highly accurate measurement. The sizes of the containers
must be proportional to the size of the flowmeter.
3.6.5 Open discharge
Figure 3-7: Installing in difficult situations
1 Use a container 2 if the Inlet pipe has a slope > 1%. Make sure that the outlet level of this pipe is below the inlet to the
flowmeter.
2 Inlet container
3 Inlet section of 10 DN
4 Outlet section of 5 DN
5 Outlet container advisable if outlet pipe has a slope > 1%.
CAUTION!
Always use a free exit pipe to prevent backflow in the flow sensor and to keep the velocity at the
maximum flow at least at 1 m/s.
Figure 3-8: Open discharge
1 ≥ 5 DN
2 Make sure that the water level stays below the pipe outlet.