Sirius 87, En - 67, General rcd with i – HT instruments SIRIUS87 User Manual
Page 69: 10ma
![background image](/manuals/367533/69/background.png)
SIRIUS
87
EN - 67
- Tripping time (t
N
)
Measuring range (ms)
Resolution (ms)
Accuracy
½ I
N
, I
N
1
999
2 I
N
1
200 general
1
250 selective
5 I
N
RCD (*)
1
50 general
1
160 selective
1
(2% rdg + 2 dgt)
(*) ”Man 5 I
n
” and “AUTO” test modes aren’t available for RCD type A
500mA
- Earth resistance R
A
without RCD tripping
Measuring range (
) Resolution
(
)
Accuracy
1
1999
1
-0%, +(5% rdg + 3 dgt)
Test current
0.5 I
N
set in U
t
test mode
15mA in Ra 15mA test
- Tripping current for RCD type A and AC
General RCD with I
N
10mA
RCD type
Measuring range I
N
(mA)
Resolution (mA)
Accuracy
AC
(0,5
1,4) I
N
0,1 I
N
-0%, +10% I
N
A
(0,5
2,4) I
N
General RCD with I
N
10mA
RCD type
Measuring range I
N
(mA)
Resolution (mA)
Accuracy
AC
(0,5
1,4) I
N
0,1 I
N
-0%, +10% I
N
A
(0,5
2) I
N
- AC voltage
Measuring range (V)
Resolution (V)
Accuracy
0
460
1
(3% rdg + 2 dgt)
- Frequency
Measuring range (Hz)
Resolution (Hz)
Accuracy
47,0
63,6
0,1
(0,1% rdg + 1 dgt)
- Line impedance (phase to phase or phase to neutral)
Measuring range (
) Resolution
(
) (*)
Accuracy
0,01
19,99
0,01
(5% rdg + 3 dgt)
20,0
199,9
0,1
(*) 0.1m
in the range 0.0 199.9 m (with IMP57)
Max peak test current
127V
3,65A
230V
6,64A
400V
11,5A
Phase to phase test voltage
100
460V 50Hz 0,5Hz
Phase to neutral test voltage
100
265V 50Hz 0,5Hz
- Fault loop impedance (phase to ground)
Measuring range (
) Resolution
(
) (*)
Accuracy
0,01
19,99
0,01
(5% rdg + 3 dgt)
20,0
199,9
0,1
200
1999
1
(*) 0.1m
in the range 0.0 199.9 m (with IMP57)
Max peak test current
127V
3,65A
230V
6,64A
Phase to earth test voltage
100
265V 50Hz 0,5Hz