Canadian Versions of SLC Devices
CRF-300
CRF-300A
Relay Control Module is similar to the CMF-300(A) except used as
a Form-C control relay module.
Fault Isolator Module
I300
I300A
The Fault Isolator Module protects the system against wire-to-wire
short circuits on the SLC. It should be placed between groups of
sensors in a Style 6 or Style 7 SLC to isolate short- and open-circuit
problems and protect the rest of the loop so it can continue to
operate normally. It is not addressable, but listed here due to its use
in an SLC.
Multi-input/output modules
MMF-300-10
MMF-300-10A
Supervises ten Class-B addressable Initiating Device Circuits (IDC)
which monitor normally open contact initiating devices.
MMF-302-6
MMF-302-6A
Monitors six zones of conventional two-wire detectors.
CDRM-300
CDRM-300A
Dual Class B monitor / Form-C relay module.
CMF-300-6
CMF-300-6A
Similar in operation to the CMF-300, except it can activate six (6)
Style Y (Class B) or three (3) Style Z (Class A) NACs.
CRF-300-6
CRF-300-6A
Similar in operation to the CRF-300, except it provides six (6) Form-
C relays.
UL-listed SLC Device
ULC-listed SLC Device
Description