18
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Wiring Requirements
Control Panel Terminal Blocks
2.4 Control Panel Terminal Blocks
The terminal blocks on the control panel circuit board that concern the SLC circuit are described
below. For more information on this subject refer to the control panel’s Instruction Manual.
2.4.1 MS-9200
TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.
TB6 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
2.4.2 MS-9600, MS-9600LS, & MS-9600UDLS
TB3 provides two types of 24 VDC power; Nonresettable and Resettable.
TB8 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules) while operating in CLIP mode.
318 addresses are available per loop (159 detectors and 159 modules) while operating in LiteSpeed
mode.
TB6
SHIELD
SLC
SLC
TB4
SL
C
-9
200
tb
.wmf
SLC
Return
SLC Out
Connections for wire shield
Unregulated Power
Nonresettable Power
Resettable Power
Figure 2.6 MS-9200 Terminal Blocks
TB8
SHIELD
SLC
SLC SLC SLC
TB3
SLC Return
SLC Out
Connections for
wire shield
Nonresettable
Power
Resettable Power
S
L
C
-960
0t
b.w
m
f
Figure 2.7 MS-9600 Series Terminal Blocks