Section 8: multiple input/output modules, 1 description, 2 cdrm-300 installation & wiring – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual
Page 54: 1 setting an slc address for a cdrm-300 module, Description 8.2: cdrm-300 installation & wiring, Setting an slc address for a cdrm-300 module
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
54
Section 8: Multiple Input/Output Modules
8.1 Description
The CDRM-300 is an addressable module that functions as two individual relay control modules
(two isolated sets of Form-C relay contacts) and two Class B monitor modules.
Ratings for the relay contacts on the module are:
8.2 CDRM-300 Installation & Wiring
8.2.1 Setting an SLC address for a CDRM-300 Module
Each module is factory preset with an address of “00”. To set an SLC address, use a screwdriver to
adjust the rotary switches on the module to the desired address. Each module can use up to four (4)
addresses. The base address selected via the rotary address switches will be assigned to relay output
#1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to
monitored input #1, relay output #2, and monitored input #2.
Load Description
Application
Maximum
Voltage
Current
Rating
Inductive (PF = 0.35)
Non-Coded
25 VAC
2.0 A
Resistive
Non-Coded
30 VDC
3.0 A
Resistive
Coded
30 VDC
2.0 A
Inductive (L/R = 20ms)
Non-Coded
30 VDC
0.46 A
Inductive (PF = 0.35)
Non-Coded
70.7 VAC
0.7 A
Resistive
Non-Coded
125 VDC
0.9 A
Inductive (PF = 0.75)
Non-Coded
125 VAC
0.5 A
Inductive (PF = 0.35)
Non-Coded
125 VAC
0.3 A
NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.