Control Modules
Wiring a CMF-300-6 Module
6.5.2 Wiring a Style Z NAC (Four-Wire)
A supervised and power-limited NFPA Style Z (Class A) NAC with a single power supply dedi-
cated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are
shown connected to the module in a four-wire configuration.
•
See “Power Considerations” on page 61 for information on monitoring 24 VDC power.
•
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
•
24 VDC power must be provided from a UL listed power supply for fire protection use.
•
A power supervision relay is required only on the last module of the power run.
•
Do not T-tap or branch a Style Z circuit.
•
Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.