Appendix e: canadian versions of slc devices – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual
Page 74

74
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Appendix E: Canadian Versions of SLC Devices
UL-listed SLC Device
ULC-listed SLC Device
Description
AD350/AD355
AD350A/AD355A
Intelligent detector that combines a photoelectric sensing chamber
and fixed temperature heat detection (135°F/57.2°C).
CP350/CP355
CP350A/CP-355A
Addressable, intelligent smoke detector that incorporates an
ionization sensing chamber. Designed to provide open area
protection.
SD350/SD355
SD350A/SD355A
Addressable intelligent smoke detector that uses a photoelectric
sensing chamber. Listed for use in ducts. Designed to provide open
area protection.
SD350T/SD355T
SD350TA/SD355TA
Adds thermal sensors that will alarm at a fixed temperature of
135°F (57°C).
H350/H355
H350A/H355A
Intelligent thermistor sensing circuit for fast response. Designed to
provide open area protection with 50 foot spacing capability. A fixed
temperature sensor with 135°F fixed temperature alarm.
H350R/H355R
H350RA/H355RA
Incorporates a thermal rate of rise of 15°F (9.4°C).
H355HT
H355HTA
High temperature sensor with 190°F (87.8°C) fixed temperature
alarm.
Photoelectric Duct Detector, Low-flow. Requires
SD350(A)/SD355(A) detector.
Bases
B210LP
B210LPA
Standard U.S. Low-Profile base (6", 15.24 cm).
B501
B501A
Standard European flangeless base (4", 10.16 cm).
B501BH, B501BHT
B501BHA, B501BHTA
Sounder base, includes Sounder base with temporal sounder (UL
8th Edition).
B501BH-2, B501BHT-2
N/A
Sounder base, includes Sounder base with temporal sounder (UL
9th Edition).
B224RB
B224RBA
Low Profile Intelligent relay base.
B224BI
B224BIA
Low Profile Intelligent isolator base.
B200SR
B200SRA
Intelligent sounder base, temporal or steady.
Monitor and Zone Interface Modules
MMF-300
MMF-300A
Used for normally open contact alarm initiating devices, such as
manual pull stations, four-wire smoke detectors, heat detectors,
waterflow, and supervisory devices.
MMF-302
MMF-302A
Used to interface with two-wire smoke detectors in addition to
normally open contacts.
MDF-300
MDF-300A
Two independent 2-wire Initiating Device Circuits (IDCs) at two
separate, consecutive addresses. Wire supervised IDCs as NFPA
Style B (Class B) or Style D (Class A) circuits. The modules come
with a thermoplastic cover for mounting to a 4-inch (10.16 cm)
square mounting box.
MMF-301
MMF-301A
Functionally similar to the MMF-300 Monitor Module, but offered in
a smaller package for mounting directly in the electrical box of the
device being monitored. (Class B input circuit only.)
BG-12LX
BG-12LX
An addressable manual pull station with key-lock reset feature. The
addressable module is housed within the pull station.
Control Modules
CMF-300
CMF-300A
Control Module, NAC: Addressable Control Module used as
Notification Appliance Circuits (NACs) to power and supervise
compatible, UL-listed notification appliances. Wired supervised
NACs as NFPA Style Y (Class B) or Style Z (Class A). The modules
come with a thermoplastic cover for mounting to a 4-inch (10.16
cm) square mounting box.