9.2.3 Wiring an Isolator Base
The B224BI Isolator Base will isolate its detector from short circuits that occur on the SLC con-
nected at terminals 2 and 3. It will not isolate its installed detector from short circuits that occur on
the SLC connected at terminals 1 and 2. In Style 7 applications, the loss of a single detector during
a short circuit is not acceptable, and an isolator module must be installed as shown in the figure
below.
9.2.4 Wiring a Relay Base
Figure 9.3 shows typical wiring of a B224RB plug-in relay detector base connected to an SLC.
–
+
–
+
SLC Out
SLC In
Conduit
I300 Isolator Module
sl
c-
22
4b
i2
w
ire
.w
m
f
Figure 9.2 Wiring of a B224BI Isolator Base Mounting Plate
Note: The “grid” pattern on the
redesigned B224BI mounting
plate has been removed for
illustration purposes only.
+ -
+ -
sl
c-
b
22
4
rb
2
w
ir
e.
w
m
f
Figure 9.3 Wiring of a B224RB Relay Base Mounting Plate