Mmf-302-6 interface module – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual
Page 30
30
FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011
Monitor Modules
Descriptions
MMF-302-6 Interface Module
This monitor module is intended to interface between the FACP and a conventional alarm system
with up to six (6) Style B (Class B) or three (3) Style D (Class A) IDCs containing normally open
contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up
to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.
– +
– +
T6
J1
BASE ADDRESS +0
BASE ADDRESS +1
BASE ADDRESS +2
BASE ADDRESS +3
BASE ADDRESS +4
BASE ADDRESS +5
A/B
S
E
L
E
CT
A/B
S
E
L
E
CT
DI
SA
BL
E 1
DI
SA
BL
E 2
T1
T0
T2
T3
T4
T5
SW1
B
A
S
E
AD
DR
E
S
S
0
1
2
3
4 5
6
7
8
9
10
11
13
14
15
12
0
1
2
3
4 5
6
7
8
9
– +
– +
– +
– +
– +
– +
– +
– +
Disable Address
Place shunt in:
Disable 1 position to disable highest module address
Disable 2 position to disable highest two module addresses
Style Y or Style Z Select
Remove shunt for Style Z circuits
SLC Address
Set rotary switches to base
(first) address of modules
Figure 5.4 MMF-302-6 Interface Module