MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Master Programming Level

A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 012. When the last digit is keyed-in, if the selected address
has not been added to programming, a screen showing information about a device that is installed
with a lower address, closest to the selected address, will be displayed. If no modules are installed
on the loop, the following screen will be displayed:

If the selected address has been added to programming but a module (such as a monitor module)
with the selected address is not physically installed on the SLC or has a communication fault, the
following screen will be displayed:

If the selected address has been added to programming and a module (such as a monitor module)
with the selected address is physically installed on the SLC and is communicating with the control
panel, the following screen will be displayed:

To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Monitor screens.
In the preceding example:

• Normal - indicates that the module with the selected address is physically installed on the

SLC and communicating with the control panel (enabled).

- represents the adjective and noun, which have been programmed,

describing the location of the displayed device.

• ZNNN - represents the first of five possible software zones that the module is assigned to

(NNN = the two digit zone number from 000 - 099).

• 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module

and 012 = Module Address 012).

If the selected address corresponds to a control module, a screen displaying information about the
control module with the selected address will be displayed as shown in “Edit Module Screen for
Control Modules” on page 88.

NO MODULE

INSTALLED

Edit Module Screen

TROUBL MONITOR

ZNNN

1M012

NORMAL MONITOR

ZNNN