The total worst case current is calculated as follows:
Using this value and referring to the Wiring Distance Table 1.1 on page 24, it can be found that the
available options are:
•
463 feet maximum using 22 Gauge wire
•
1,172 feet maximum using 18 Gauge wire
•
1,866 feet maximum using 16 Gauge wire
•
2,953 feet maximum using 14 Gauge wire
Wiring Configuration
Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-80 Current Draw
= 3 X 0.040 amps
= 0.120 amps
ANN-S/PG Current Draw
= 1 X.0.040 amps
= 0.040 amps
ANN-I/O Current Draw
= 1 X.0.200 amps
= 0.200 amps
Total Worst Case Current Draw
= 0.360 amp