1 dact-ud2 installation, Dact-ud2 installation – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual
Page 52
52
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Installation
Optional Modules and Devices
2.6.1 DACT-UD2 Installation
The DACT-UD2 Digital Alarm Communicator/Transmitter, which is supplied standard with the
MS-9600UDLS/E, transmits system status to UL listed Central Station receivers via the public
switched telephone network. It is capable of reporting up to 99 software zones or up to 636
addressable points. Two modular phone jacks, labeled PRI for Primary phone line and SEC for
Secondary phone line, allow easy connection of two independent telephone lines to the DACT-
UD2. The following functions have been incorporated into the DACT-UD2:
•
Line Seizure - takes control of phone lines disconnecting any premises phones
•
Off/On Hook - performs on and off-hook status to the phone lines
•
Listen for dial tone - 440 hertz tone typical in most networks
•
Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
•
For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’
tone(s) - the frequency and time duration of the tone(s) varies with the transmission format.
The control panel will adjust accordingly
•
Communicate in the following formats:
• Ademco Contact ID
• SIA
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
!
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
Figure 2.11 DACT-UD2 Module
SEC
Secondary Phone Line
J5 Connector (located on
back of module) plugs into J2
on FACP main circuit board
PRI
Primary Phone Line
DIAL
X
.wmf
J4
USB Port