2.6.1 DACT-UD2 Installation

The DACT-UD2 Digital Alarm Communicator/Transmitter, which is supplied standard with the
MS-9600UDLS/E, transmits system status to UL listed Central Station receivers via the public
switched telephone network. It is capable of reporting up to 99 software zones or up to 636
addressable points. Two modular phone jacks, labeled PRI for Primary phone line and SEC for
Secondary phone line, allow easy connection of two independent telephone lines to the DACT-
UD2. The following functions have been incorporated into the DACT-UD2:

Line Seizure - takes control of phone lines disconnecting any premises phones

Off/On Hook - performs on and off-hook status to the phone lines

Listen for dial tone - 440 hertz tone typical in most networks

Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary

For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’
tone(s) - the frequency and time duration of the tone(s) varies with the transmission format.
The control panel will adjust accordingly

Communicate in the following formats:
• Ademco Contact ID
• SIA

The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.

!

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.

Figure 2.11 DACT-UD2 Module

SEC

Secondary Phone Line

J5 Connector (located on
back of module) plugs into J2
on FACP main circuit board

PRI
Primary Phone Line

DIAL

X

.wmf

J4
USB Port