beautypg.com

Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 29

background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

29

Accessories

Product Description

Wiring ANN-80 to FACP

The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.

1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal

block TB1.

2. Remove appropriate amount of wire insulation.
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).

Make certain to connect A to A and B to B.

4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals

3 & 4. Make certain to connect A to A and B to B.

5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+).

Make certain to observe proper polarity.

6. If appropriate, connect the power wiring going to the next device to terminals

1 (-) & 2 (+). Make certain to observe proper polarity.

7. After all connections are made, remove extra wire from inside of annunciator by dressing it

neatly through wire channel, with any excess wire pushed back through hole into electrical
box.

wiring channel

wires

TB1

an

n-

80

bo

xi

n

side

.wmf

TB1

B A (+) (-)

4 3 2 1

TB3

JP5

TB4

JP8

TB5

TB6

TB1

+ - + - + -

A B

+ -

Figure 1.6 ANN-80 Wiring to FACP

FACP

ANN-80

ANN-BUS and power wiring are

supervised and power-limited

24 VDC
nonresettable

ANN-BUS

960

0

ls

to

an

n80

.cd

r

ANN-BUS/
ACS BUS