2 zones, Zones – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 163

background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

163

Read Status

Operating Instructions

Pressing the down arrow key, while viewing the screen shown on the previous page, will allow the
operator to view additional programming information about the selected device, such as:

Enable/Disable Status

Device Type

Alarm Verification On/Off

Walktest Yes/No

PAS (Positive Alarm Sequence) Yes/No

Pre-Signal Yes/No

Zone Assignments (five maximum)

Chamber Reading

Adjective/Noun descriptor

Silenceable Yes/No (for control modules)

4.22.2 Zones

Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:

From the preceding screens, the control panel operator can view:

Zones Installed - all software zones programmed into the system (99 maximum)

Zones Enabled - all software zones that are enabled

Zones Disabled - all software zones that have been disabled

Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98
reserved for Pre-signal and 99 reserved for future use

Zone Type - the Type assigned to each installed zone (default is Alarm)

Zone Message - the message assigned to each installed zone

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

Read Status Screen #1

ZONES

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zones Screen #1

ZONES

1=SPECIAL PURPOSE

2=ZONE TYPE

3=ZONE MESSAGE

Zones Screen #2