beautypg.com

Ann-s/pg serial/parallel interface installation – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 30

background image

30

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Product Description

Accessories

The following table shows the ANN-80 connections to the FACP

Programming

Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must added to the system via FACP programming. Refer to the programming section titled “ANN-
BUS Options” on page 121 in thi
s manual for detailed programming information. Select the LCD
option for programming.

Trouble Response

If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble
and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.

To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.

If the Keyswitch on the ANN-80 is left in the unlocked position for more than 2 minutes, a trouble
condition will be indicated at the FACP.

ANN-S/PG Serial/Parallel Interface Installation

The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel
printer to the FACP for a real-time log of system events, detector status reports and event history.
The module is provided with a plastic enclosure for surface mounting. Proceed with the installation
as described in the following:

1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.7.

3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)

to the module.

FACP

ANN-80 (TB1)

Terminal GND (-) on TB3

Terminal 1 (-)

Terminal PWR (+)TB3

Terminal 2 (+)

Terminal ACS on TB6

Terminal 3 (A)

Terminal ACS on TB6

Terminal 4 (B)

(-)

(+)

A
B

TB3

JP5

TB4

JP8

TB5

TB6

TB1

+ - + - + -

+ -

A B

Figure 1.7 ANN-S/PG Connection to FACP

ANN-S/PG Module

FACP

Cable Connectors for
connection to printer

Parallel

Serial

ANN-BUS and power wiring are
supervised and power-limited

24 VDC
nonresettable

ANN-BUS/
ACS BUS

96

00

lst

o

spg

.w

m

f