beautypg.com

Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 24

background image

24

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Product Description

Accessories

capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maxi-
mum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula
used to generate this chart is shown in the note below.

The following formulas were used to generate the wire distance chart:

Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:

Wiring Distance Calculation Example:

Suppose a system is configured with the following ANN-BUS modules:

3 ANN-80 Remote Fire Annunciators

1 ANN-S/PG Serial/Parallel Printer Interface Module

1 ANN-I/O LED Driver Module

Wiring Distance: ANN-BUS Modules to FACP

Total Worst Case Current

Draw (amps)

22 Gauge

18 Gauge

16 Gauge

14 Gauge

0.100

1,852 ft.

4,688 ft.

* 6,000 ft.

*6,000 ft.

0.200

926 ft.

2,344 ft.

3,731 ft.

5,906 ft.

0.300

617 ft.

1,563 ft.

2,488 ft.

3,937 ft.

0.400

463 ft.

1,172 ft.

1,866 ft.

2,953 ft.

0.500

370 ft.

938 ft.

1,493 ft.

2,362 ft.

Table 1.1 Wiring Distances

Maximum Resistance (Ohms)

=

6.0 volts

Total Worst Case Current Draw (amps)

Maximum Wire Length (feet)

(6,000 feet maximum)

=

Maximum Resistance (Ohms)

*500

Rpu

where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)

Wire Gauge

Ohms per 1,000 feet (Rpu)

22

16.2

18

6.4

16

4.02

14

2.54

Wire Gauge

Maximum Wire Length

18

312 feet

16

497 feet

14

787 feet

12

1,250 feet