Fire-Lite MS-4E Fire Alarm Control Panel User Manual
Page 34
34
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Program Options via DIP Switch
DIP Switch Settings
Switch Number
DIP Switch Number
DIP Switch ON
SW1
1
Silence Inhibit
2
Auto-silence
3
Temporal Coding
4
Selective Silence (if sync. enabled)
5
Trouble Reminder
6
AC Trouble Delay
7
Autoresettable Supervisory
8
IDC Combination
Waterflow/Supervisory Circuit
SW2
1
IDC1 Verification
2
IDC1 Supervisory
3
IDC2 Verification
4
IDC2 Supervisory
5
IDC3 Verification
6
IDC3 Supervisory
7
IDC4 Verification
8
IDC4 Supervisory
SW3
1
NAC1 Nonsilenceable
2
NAC1 Disable
3
NAC2 Nonsilenceable
4
NAC2 Disable
5 & 6
used to select strobe
synchronization feature as
shown to the right
Switch 5
Switch 6
No Synchronization
OFF
OFF
System Sensor Synchronization
ON
OFF
Gentex Synchronization
OFF
ON
Wheelock Synchronization
ON
ON
7
Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)
8
spare
Table 3.2 MS-4 DIP Switch Settings