4xtmf transmitter module installation, Standoffs (when using j4 & j6 – Fire-Lite MS-4E Fire Alarm Control Panel User Manual
Page 27
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
27
Installation of Optional Modules
Installation
The following steps must be followed when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules.
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6) on the main
circuit board to allow the control panel to supervise the placement of any installed option
module.
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide the
required earth ground protection.
4. Carefully plug the connectors on the option module into connectors J3 and J5 or J4 and J6 on
the FACP main circuit board, being careful not to bend any pins.
5. Secure the option module to the standoff on the main circuit board with the supplied screws.
6. When the installation has been completed, connect the wiring to the modules as indicated in
the following sections.
7. Test system for proper operation.
4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK
TEST
ALARM
SILENCE
ZONE
DISABLE
FIRE ALARM
FIRE ALARM
RESET
WALK
TEST
ALARM
SILENCE
ACK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE
ENABLE/DISABLE
3
4
2
1
TB
1
TB
2
TB
3
TB5
TB
6
TB7
J1
B+ B- B+ B-
NAC 1 NAC 2
+ - + -
Nonreset Reset
B+ B- B+ B-
ZONE 1 ZONE 2
B+ B- B+ B-
ZONE 3 ZONE 4
C TRBL NORM
TROUBLE
C NC NO
ALARM
SUPV
C NC NO
J3
J5
J4
J8
J7
J9
TB8
J6
JP1
JP3
SW1
BATTERY
HOT NEUT EARTH
TR
A
N
SF
O
R
M
E
R
1
TRA
N
SF
ORM
E
R 2
SW2 SW3
JP2
EARTH BATT CHG
CLASS A
CONVERTER
Figure 2.12 4X Option Module Connection to MS-4
J3
J5
J4
J6
JP1 Jumper
Cut to install
module on J3 & J5
JP2 Jumper
Cut to install module on J4 & J6
Standoffs
(when using
J3 & J5
ms4bord2.wmf
Standoffs
(when using
J4 & J6