4xlmf led interface module (ms-4 only), Figure 2.15 4xlmf led interface module – Fire-Lite MS-4E Fire Alarm Control Panel User Manual
Page 30
30
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Installation
Installation of Optional Modules
4XLMF LED Interface Module (MS-4 only)
The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must
follow the requirements as specified in “Power-limited Wiring Requirements” on page 24.
Important: The 4XLMF module can only be installed on connectors J3 and J5 of the MS-4 main
circuit board.
4XLB
Figure 2.15 4XLMF LED Interface Module
Front View of RZA-4XF
Side View
Single-gang Box
4XLMF Module
Note: Make wiring connections with system
power off. Maximum wire impedance is
50 ohms per wiring connection.
+24 VDC
Out #1