MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Installation
Installation of Optional Modules
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for 
connection to a polarity reversal circuit or a Remote Station receiving unit having 
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to 
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate 
after the module is installed in the FACP. In addition, the System Trouble LED will turn on to 
indicate the Disconnect condition. 
Figure 2.13 4XTMF Transmitter Module
Connect to: 
• MS-4 Connectors J3 & J5 or J4 & J6
• MS-2 Connectors J3 & J5.
Disconnect 
Switch 
shown in 
disconnect 
position
TBL Jumper
Remote Alarm (power-limited)*
Remote Trouble (power-limited)*
No connection
Municipal Box (nonpower-
limited)*
1+
2-
3+
4-
5
6+
7-
Polarities are shown for module activation
Note: 4XTMF Module is not suitable for transmitting reverse 
polarity supervisory signal.
* Wiring from these terminals 
can exit the protected premises. 
Dummy load terminals 6 and 7 
(4.7k
, ¼ watt resistor) if
Municipal Box is not connected.