Fire-Lite MS-4E Fire Alarm Control Panel User Manual
Page 13
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
13
Controls and Indicators
Product Description
•
Walktest
•
Zone Enable/Disable - Zone 1
•
Zone Enable/Disable - Zone 2
•
Zone Enable/Disable - Zone 3 (MS-4 only)
•
Zone Enable/Disable - Zone 4 (MS-4 only)
LED Indicators
•
Fire Alarm Zone 1 - red LED
•
Fire Alarm Zone 2 - red LED
•
Fire Alarm Zone 3 - red LED (MS-4 only)
•
Fire Alarm Zone 4 - red LED (MS-4 only)
•
Supervisory Zone 1 - yellow LED
•
Supervisory Zone 2 - yellow LED
•
Supervisory Zone 3 - yellow LED (MS-4 only)
•
Supervisory Zone 4 - yellow LED (MS-4 only)
•
Trouble Zone 1 - yellow LED
•
Trouble Zone 2 - yellow LED
•
Trouble Zone 3 - yellow LED (MS-4 only)
•
Trouble Zone 4 - yellow LED (MS-4 only)
•
Maintenance Zone 1 - yellow LED
•
Maintenance Zone 2 - yellow LED
•
Maintenance Zone 3 - yellow LED (MS-4 only)
•
Maintenance Zone 4 - yellow LED (MS-4 only)
•
AC Power - green LED
•
NAC Disable - yellow LED
•
Zone Disable - yellow LED
•
NAC Fault - yellow LED
•
System Trouble - yellow LED
•
Power Trouble - yellow LED
•
Walktest - yellow LED
•
Alarm Silence - yellow LED
•
Earth Fault - yellow LED (on main circuit board) lights if zero impedance between FACP and
ground exists
•
Battery Fault - yellow LED (on main circuit board)
•
Charger Fault - yellow LED (on main circuit board)
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse ½ second on and ½ second off
•
Supervisory - pulse ½ second on and ½ second off