rouGh In dIMensIons

InstallatIon consIderatIon

table 1 – rough-In-dimensions

Units

A

B

C

D

E

F

G

H

I

Inches 66.75

49.25

22.00

15.75

3.00

8.00

8.00

62.00

65.00

cm

169.5 125.09 55.88

40.00

7.62

20.32

20.32

157.48

165.1

top/side Inlet and outlet: 3/4” npt

Gas Inlet: 1/2” npt

table 2 – capacity, Gas and electrical characteristics

Approximate Capacity

Manifold Pressure

Electrical Characteristics

U.S. Gals.

Liters Gas Type

“WC

kPA

Volts/Hz

Amperes

50

189

Nat./LP

0”

0”

120/60

<5

all models - Maximum supply pressure: 14 inches w.c. (3.48kpa)

Minimum supply pressure for natural Gas: 3.50” (.87kpa)

Minimum supply pressure for propane Gas: 8.00” (1.99kpa)

Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.

table 3 – recovery capacities - u.s. Gallons/hr. and liters/hr. at temperature rise Indicated

Input

Recovery Capacities

Rating

(Btu/hr)

Rating

(kW)

Temp.

Rise

F

30

40

50

60

70

80

90

100

110

120

130

140

C

17

22

28

33

39

44

50

56

61

67

72

78

100,000

29.3

GPH

387

291

233

194

166

145

129

116

106

97

90

83

LPH

1465

1102

882

734

628

549

488

439

401

367

341

314

Recovery capacity based on 96% thermal efficiency