American Water Heater VG6250T100 User Manual

Page 42

background image

42

dIsplaY settInGs

descrIptIon/actIon

dIsplaY

Select Display Settings from the Main Menu and press the

Operational Button under "SELECT" to enter this menu. This menu

contains adjustable display options for viewing information on the

LCD screen. Use the Up & Down Buttons to navigate the menu.

temperature units - Adjustable user setting that changes

temperature units display to Celsius °C or Fahrenheit °F.

backlight delay - Adjustable user setting that determines how

long the LCD backlight remains illuminated after a key has

been pressed. Available settings are; Always Off, 10, 30 or 60

seconds and Always On.

contrast - Adjustable user setting to adjust the LCD screen

contrast between text and background.
note: These settings are adjusted in the same way described

for the Operating Set Point and Differential Adjustment.

Temperature Units

°F

Backlight Delay

30s

Contrast

60%

CHANGE

BACK

HELP

Display Settings

heater InforMatIon

descrIptIon/actIon

dIsplaY

Select Heater Information from the Main Menu and press the

Operational Button under "SELECT" to enter this menu. This menu

contains non adjustable operational information.

elapsed time - Total accumulated time the control system

(water heater) has been energized.

burner on time - Total accumulated time the control system

has been in the heating operating state; burner run time.

cycle count - Total accumulated count of heating cycles.

ccb version - Software version for central control board.

uIM version - Software version for user interface module.
note: Historical data is stored in the CCB's memory. If this CCB

is replaced during servicing the historical data on the CCB being

replaced will be lost. The data stored in the new circuit board will

no longer reflect the entire history of the water heater.
The Elapsed Time, Burner On Time and Cycle Count indicate

age, usage and wear.
If the Cycle Count per day is high (divide cycle count by days

to determine cycles per day) or the cycle duration is short

(determine burner on time total minutes, divide burner on time

total minutes by cycle count) consider rasing the Differential

setting to avoid short cycling and excessive component wear,

see Operating Set Point and Differential Adjustment.
This historical data can also be used to assist facilities managers

in forecasting planned replacement of equipment to help avoid

lengthy and costly hot water supply interruptions.

Elapsed Time

10 day 0 hrs 0 mins

Burner On Time

5 hrs 22 mins

Cycle Count

00000035

CCB Version

X.XX

UIM Version

X.XX

CHANGE

BACK

HELP

Heater Information