beautypg.com

User settings & control system menus – American Water Heater VG6250T100 User Manual

Page 40

background image

40

user settInGs & control sYsteM Menus

teMperatures

operatInG set poInt and dIfferentIal adjustMent

The Operating Set Point is adjustable from 90°F (42°C) to 180°F (82°C) for commercial and 160°F (71°C) on residential models. The factory

setting is 120°F (49°C). The Differential is adjustable from 2° to 20°. The factory setting is 8°. These user settings are accessed from the

Temperatures menu. These instructions explain how to adjust these settings and navigate the control system.

When the water temperature sensed by the control system from the Temperature Probe reaches the Operating Set Point the control system

will end the heating cycle. A heating cycle will be activated again when the sensed water temperature drops below the Operating Set Point

minus the Differential setting.

note: Set the Operating Set Point to the lowest setting which produces an acceptable hot water supply for most efficient use. Lower

Differential settings may cause excessive heating cycles (short-cycling) which can cause premature failure of components such as the

Igniter. Set the Differential at the highest setting which produces an acceptable hot water supply to prevent short cycling.

descrIptIon/actIon

dIsplaY

From the Desktop screen, press the Operational Button under

MENU. The "Main Menu" screen will be displayed.

Tank Temperature

120°F

Operating Set Point

120°F

Status: Standby

MENU

HELP

MANUFACTURER / MODEL INFORMATION

The Main Menu is where all control system menus are listed,

see Table 11 for a complete list and description of control

system menus. Use the Up and Down Buttons to view all

control system menus from the Main Menu.

With Temperatures menu selected (highlighted in black) in

the Main Menu screen, press the Operational Button under

“SELECT” to enter the Temperatures menu.

If the Temperatures menu is not selected use the Up and Down

Buttons to select this menu item.

Temperatures

Heater Status

Display Settings

Heater Information

Current Fault

SELECT

BACK

HELP

Main Menu

With the Operating Set Point selected in the Temperatures

menu, press the Operational Button underneath “CHANGE” to

activate the adjustment mode for this menu item.

If Operating Set Point is not selected use the Up and Down

Buttons to select this menu item.

note: Higher Temperature settings increase wear and

operating costs. Set the Operating Set Point to the lowest

setting which produces an acceptable hot water supply. This

will always provide the most energy efficient operation and

longer life.

Operating Set Point

120°F

Differential

8°F

Tank Temperature

120°F

Tank Probe Offset 0°F

CHANGE

BACK

HELP

Temperatures

With the adjustment mode for the Operating Set Point activated

the selection bar will change from a black fill to a black outline.

Use the Up and Down Buttons to change the current setting.

Press the Operational Button under "UPDATE" to save the

new setting. Press the Operational Button under "CANCEL" to

discard changes and return to the previously saved setting.

note: Use this same procedure to change the Differential

setting and other adjustable user settings in the control system

menus.

Operating Set Point

140°F

Differential

8°F

Tank Temperature

120°F

Tank Probe Offset

0°F

UPDATE

CANCEL

Temperatures