Termination clearances sidewall power vent – American Water Heater VG6250T100 User Manual

Page 23

background image

23

terMInatIon clearances sIdewall power vent

V

X

VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

v

v

A

G

V

FIXED

CLOSED

FIXED

CLOSED

OPERABLE

OPERABLE

V

C

B

B

B

B

F

B

V

V

A

J

V

H

M

X

X

V

V

K

B

E

D

L

POWER VENT

(using room air for combustion)

EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION

fIGure 13

Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion.

us InstallatIons 1

us InstallatIons 1

a

Clearance above grade,

veranda, porch, deck or

balcony

12 inches (30 cm)

h

Clearance to each side

of center line extended

above meter/regulator

assembly

3 feet (91 cm) within a

height 15 feet (4.5 m)

above the meter/regulator

assembly*

b

Clearance to window

or door that may be

opened

4 feet (1.2 m) below

or to side of opening;

1 foot (30 cm) above

opening

I

Clearance to service

regulator vent outlet

3 feet (91 cm)*

c

Clearance to

permanently closed

window

12 inches (30 cm)*

j

Clearance to a non

mechanical air supply

inlet into building or

combustion air inlet to

any other appliance

4 feet (1.2 m) below or to

side of opening; 1 foot

(30 cm) above opening.

d

Vertical clearance to

ventilated soffit located

above the terminal

within a horizontal

distance of 2 feet (61

cm) from the center line

of the terminal

12 inches (30 cm)*

K

Clearance to a

mechanical air supply

inlet

3 feet (91 cm) above if

within

10 feet (3 m) horizontally

e

Clearance to

unventilated soffit

12 inches (30 cm)*

l

Clearance above paved

sidewalk or paved

driveway located on

public property

7 feet (2.13 m)

f

Clearance to outside

corner

2 feet (60 cm)*

M

Clearance under

veranda, porch, deck, or

balcony

12 inches (30 cm) ‡

G

Clearance to inside

corner

18 inches (45 cm)*

1 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.