American Water Heater VG6250T100 User Manual
Page 41
41
teMperatures (cont)
descrIptIon/actIon
dIsplaY
•
tank temperature - non adjustable - control system sensed
temperature from the Temperature Probe.
•
tank probe offset - adjustable user setting, range -5° to +5°
(factory setting 0°).
The Tank Probe Offset is used to calibrate control system
temperature sensing. This can improve the precision of
temperature control in the storage tank and at points of use.
This feature can also be used to compensate for building
recirculation loops (hot water returning to the storage tank) that
may cause the heating cycles to terminate prematurely.
Example: If the current sensed temperature from the temperature
probe is 120°F (49°C) and the Offset setting for the probe is
adjusted to a value other than 0°, the control system would
calibrate or “offset” the sensed temperature from the probe.
Heating cycles would be activated and deactivated based on
the calibrated (offset) temperature.
note: The Tank Probe Offset should only be used if the hot water
supply temperature varies greatly from the Operating Set Point
setting. These settings are adjusted in the same way described
for the Operating Set Point and Differential Adjustment.
Operating Set Point
140°F
Differential
8°F
Tank Temperature
120°F
Tank Probe Offset
0°F
CHANGE
BACK
HELP
Temperatures
heater status
descrIptIon/actIon
dIsplaY
Select Heater Status from the Main Menu and press the Operational
Button under "SELECT" to enter this menu. This menu contains non
adjustable operational information. Use the Up & Down Buttons to
navigate the menu.
•
status - displays the current Operating State, see Table 10 for
a description of the various operational states.
•
eco contact, blocked Inlet ps, blocked outlet ps, blower
prover ps - displays the current state of the switch contacts;
open or closed.
•
blower low on, blower high on - displays whether the
blower is running at high speed during Pre/Post purge and
the Heating operational states or the blower is running at low
speed during the Igniter Warm Up operational state; yes =
blower is running at the designated speed, no = blower is not
running at the designated speed.
•
Igniter on, Gas valve on - displays whether or not the control
system is currently energizing these water heater components;
yes = energized, no = de-energized.
•
Igniter current - displays whether or not the control system
has detected the required minimum current.
•
flame detected - displays whether or not the control system
has detected Main Burner flame during ignition from the Flame
Sensor.
• E
xternal Input enable - displays whether or not the S1
dipswitches have been configured to activate the Enable/
Disable circuit; yes = the Enable/Disable circuit has been
activated, no = the Enable/Disable circuit has not been
activated. The factory setting is "no" or deactivated.
•
Ignition trials - displays whether or not the S1 dipswitches
have been configured to allow 1 or 3 trials for ignition before
declaring an "Ignition Failure" Fault condition. The factory
setting is for 3 trials.
Top of Menu
Status
Standby
ECO Contact
Closed
Blocked Inlet PS
Closed
Blocked Outlet PS
Closed
Blower Prover PS
Open
Blower Low On
No
Blower High On
No
BACK
HELP
Heater Status
Bottom of Menu
Blower High On
No
Igniter On
No
Igniter Current
No
Gas Valve On
No
Flame Detected
No
External Input Enable
No
Ignition Trials
3
BACK
HELP
Heater Status