teMperatures (cont)

descrIptIon/actIon

dIsplaY

tank temperature - non adjustable - control system sensed

temperature from the Temperature Probe.

tank probe offset - adjustable user setting, range -5° to +5°

(factory setting 0°).
The Tank Probe Offset is used to calibrate control system

temperature sensing. This can improve the precision of

temperature control in the storage tank and at points of use.

This feature can also be used to compensate for building

recirculation loops (hot water returning to the storage tank) that

may cause the heating cycles to terminate prematurely.
Example: If the current sensed temperature from the temperature

probe is 120°F (49°C) and the Offset setting for the probe is

adjusted to a value other than 0°, the control system would

calibrate or “offset” the sensed temperature from the probe.

Heating cycles would be activated and deactivated based on

the calibrated (offset) temperature.
note: The Tank Probe Offset should only be used if the hot water

supply temperature varies greatly from the Operating Set Point

setting. These settings are adjusted in the same way described

for the Operating Set Point and Differential Adjustment.

Operating Set Point

140°F

Differential

8°F

Tank Temperature

120°F

Tank Probe Offset

0°F

CHANGE

BACK

HELP

Temperatures

heater status

descrIptIon/actIon

dIsplaY

Select Heater Status from the Main Menu and press the Operational

Button under "SELECT" to enter this menu. This menu contains non

adjustable operational information. Use the Up & Down Buttons to

navigate the menu.

status - displays the current Operating State, see Table 10 for

a description of the various operational states.

eco contact, blocked Inlet ps, blocked outlet ps, blower

prover ps - displays the current state of the switch contacts;

open or closed.

blower low on, blower high on - displays whether the

blower is running at high speed during Pre/Post purge and

the Heating operational states or the blower is running at low

speed during the Igniter Warm Up operational state; yes =

blower is running at the designated speed, no = blower is not

running at the designated speed.

Igniter on, Gas valve on - displays whether or not the control

system is currently energizing these water heater components;

yes = energized, no = de-energized.

Igniter current - displays whether or not the control system

has detected the required minimum current.

flame detected - displays whether or not the control system

has detected Main Burner flame during ignition from the Flame

Sensor.

• E

xternal Input enable - displays whether or not the S1

dipswitches have been configured to activate the Enable/

Disable circuit; yes = the Enable/Disable circuit has been

activated, no = the Enable/Disable circuit has not been

activated. The factory setting is "no" or deactivated.

Ignition trials - displays whether or not the S1 dipswitches

have been configured to allow 1 or 3 trials for ignition before

declaring an "Ignition Failure" Fault condition. The factory

setting is for 3 trials.

Top of Menu

Status

Standby

ECO Contact

Closed

Blocked Inlet PS

Closed

Blocked Outlet PS

Closed

Blower Prover PS

Open

Blower Low On

No

Blower High On

No

BACK

HELP

Heater Status

Bottom of Menu

Blower High On

No

Igniter On

No

Igniter Current

No

Gas Valve On

No

Flame Detected

No

External Input Enable

No

Ignition Trials

3

BACK

HELP

Heater Status