Blower prover failure, Blower prover open, Blocked air intake – American Water Heater VG6250T100 User Manual

Page 55: Energy cut out (eco)

background image

55

fault and alert MessaGes (cont)

Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service agent in

your area.

possIble causes - checK/repaIr

dIsplaYed fault/alert MessaGe

• The control system has detected the Blower Prover Switch

contacts are closed when they should be open at the beginning of

a heating cycle.

• Pinched/shorted Blower Prover Switch wiring.
• Jumper wire connected to the Blower Prover Switch - remove

jumper wire. Jumper wires must never be used, read all Warnings.

• Excessive wind outdoors pressurizing the vent system piping.
• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blower Prover Failure

Fault occurred 2 mins ago

The blower prover switch is

closed out of sequence.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blower Prover Switch

contacts are remaining open after the control system has

energized the Combustion Blower.

• Loose or open wiring to the Blower Prover Switch.
• Blower Prover Switch air sensing tube disconnected, kinked, filed

with condensate, damaged or leaking - repair or replace tube.

• Combustion Blower is not running when energized.
• Loose or open wiring to Combustion Blower.

CHANGE

BACK

ADVANCED

Blower Prover Open

Fault occurred 2 mins ago

The blower prover switch remains

open after the blower has been

energized.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blocked Intake Air Switch

contacts are open.

• Loose or open wiring to the Blocked Intake Air Switch.
• Excessive equivalent pipe length, exceeded the maximum number

of 90° elbows or wrong pipe size used in the intake air piping

system.

• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blocked Air Intake

Fault occurred 2 mins ago

The combustion air intake is

restricted.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the ECO (energy cut out) Switch

contacts are open.

• The ECO switch is a normally closed switch that opens on a

temperature rise to prevent excessive water temperature in the

storage tank. The ECO switch is inside the Temperature Probe

(two red wires).

• Loose or open wiring to the ECO switch in the Temperature Probe

- two red wires.

CHANGE

BACK

ADVANCED

Energy Cut Out (ECO)

Fault occurred 2 mins ago

Tank temperature is excessive.

The water heater has been

disabled.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)