beautypg.com

0 system configuration, 1 configuration, 2 touch panel graphic display – Detcon 880S-N4X User Manual

Page 7: System configuration, Configuration, Touch panel graphic display, Figure 3 back of touch panel display, A model 880 is equipped with

background image

880-N4X

880-N4X Instruction Manual

Rev. 0.0

Page 3 of 36

2.0 System Configuration


The Model 880 is designed to monitor and display the status of field sensor devices, provide programmable
alarm outputs, and log alarm incidents via a USB drive. The system is equipped with a color graphic touch
screen display. Control electronics are industry standard PLC modules pre-selected to fit the application.
Twelve 10Amp relays provide three “Banks” of four relays, each designed to give Alarm 1, Alarm 2, Alarm 3
and Fault conditions for each related bank. Each relay provides one set of contacts: Common, Normally Open,
and Normally Closed for customer annunciator connection.

2.1 Configuration


A Model 880 is equipped with:

• 8.31" x 6.24" (211.2 x 158.4 mm) Color Graphical Touch Screen display panel
• Six slot Programmable Logic Controller (PLC)

o

Two communication port CPU Module

o

Twelve channel Relay Output Module

o

Eight channel Relay Output Module

o

Communications Module (2ea.)

• Isolated Network Adapter
• 24VDC 10Amp Power Supply
• (12) 10amp 1PDT DC Alarm Relays
• Fault, Alarm, Communications, and Power Panel Indicator LED’s

2.2 Touch Panel Graphic Display


The Model 880 is equipped with a graphic display panel (Figure 3) that is prompted to display information
such as the operational status of each monitoring device, alarm output readings, and record alarm incidents to a
USB Drive.

PWR

CPU

TxD

RxD

+

Used

NOT

24V . . . .

Dedicated
power supply

recommended

PLC Serial Port

DC Input

Ethernet 10/100
Base T Connector

USB Type A Port

USB Type B Port

Audio Line Out

BACK VIEW

BOTTOM VIEW

Figure 3 Back of Touch Panel Display

This manual is related to the following products: