beautypg.com

4 remote display set-up, Remote display set-up – Detcon 880S-N4X User Manual

Page 24

background image

880-N4X

880-N4X Instruction Manual

Rev. 0.0

Page 20 of 36

1) Select “Fault” to set the Fault as latching or non-latching. When de-activated (gray), the ‘N-L’ button will

2) Select “Alarm 1” to set the level at which Alarm 1 will be activated (typically 10% of full range).

3) Select “Alarm 2” and set the level at which Alarm 2 will be activated (typically 20% of full range).

4) Select “Alarm 3” and set the level at which Alarm 2 will be activated (typically 50% of full range).

5) Next to “Alarm 1”, “Alarm 2”, and “Alarm 3”, boxes are two buttons labeled ‘ASC/DES’ and ‘LAT/N-L’

a) When activated (blue), the ‘ASC’ button will cause the associated Alarm to activate when the sensor

) When activated (blue), the ‘LAT’ button will cause the associated Alarm to be “Latching” and will not

6) At the bottom of the screen are three boxes labeled “RELAY BANK SELECT”, “1”, “2”, and “3”. These

7) Once all parameters for the sensor have been set appropriately, select “EXIT” to return to the Main Screen.

8) Proceed through all channels, setting each channel’s parameters to the desired values. When all channels

.4 Remote Display Set-up

he remote display must be setup to match the main 880. The screens are duplicates of the Main 880;

) From the “Main Screen” (Figure 26), enter the “System Configuration Screen” by touching the “System

) The display will prompt for a password to enter the 880 “System Configuration Screen”. The default

password is “1234”. Enter the password in the Pop-Up Screen and press enter to continue. This will
open the “System Configuration Screen” (Figure 27 – Analog, Figure 28 - Serial).

entry of 100 with a “Decimal Place” of 1 provides a range of 10.0, 10ppm or 10%. Likewise, a “Range”
entry of 500 with a “Decimal Place” of 2 provides a range of 5.00, 5ppm or 5%.)


1

cause the Fault to reset itself only when the fault condition is cleared or fixed. When activated (blue), the
“Fault” ‘LAT’ button will cause the Fault to be “Latching” and will not allow the Fault to reset until the
fault condition is fixed or cleared and the reset button is pressed.


1

1

1

1

dependent on the current state of the button. When activated, these buttons will turn from gray to blue.
The button labeled ‘ASC/DES’ will set the sensor alarm for ascending (ASC) or descending (DES)
respectively. The button labeled ‘LAT/N-L’ will set the sensor alarm for latching (LAT) or non-latching
(N-L) respectively. Set the appropriate values for each alarm respectively:

value rises above the value set for that Alarm (Ascending). When de-activated (gray), the ‘DES’
button will cause the associated Alarm to activate when the sensor value falls below the value set for
that Alarm (Descending). Set Alarm’s 1, 2, and 3 to either ascending or descending.


b

allow that Alarm to reset until the cause is cleared or removed and the Alarm is reset with the reset
button. When de-activated (gray), the ‘N-L’ button will cause the associated Alarm to be reset when
the cause of the alarm is either cleared or removed. Set Alarm’s 1, 2, and 3 to either latching or non-
latching.


1

Bank Selection boxes will assign each sensor to a bank of alarms. Assigning a sensor to a Bank of alarms
allows the operator to create groups of sensor Alarms. When activated (Green) the sensor will be assigned
to the bank selected. I.E., selecting Bank 1 will assign that sensor to Bank 1; therefore, should an alarm
occur, it triggers the appropriate alarm in Bank 1 only.


1

1

have been correctly set the unit should be ready for normal operation.

4


T
therefore, the setup is accomplished in much the same manner as the main unit.

1

Configuration” box with the wand.


2

This manual is related to the following products: