8.0 System

Expansions


System expansions will involve any combination of the following activities. These are covered in detail in the
previous sections of this Operators Manual. Refer to the following Checklist (Items 1 – 4) and their associated
reference sections.

1) Adding new I/O modules - See Section 3.1 on “Installing the I/O Modules”
2) Connecting to the new I/O Modules - Section 3.2 on “Connecting to the I/O Modules”
3) Setting Device Identification on the I/O Modules – See Section 4.2 on “Setting Device Identification on

the I/O Modules”

4) Configuration of the new gas sensors and relay outputs:

Select Active # of Channels and Relays – Section 5.3.1
Odbus™ Addressing and Relay Set-up – Section 5.3.2
Select Gas Type and Range – Section 5.3.3
Set Active Alarm Levels – Section 5.3.4
View Tag Information Section 5.3.6



9.0

Troubleshooting


Problem: No Communications
Check that all I/O Modules and Modbus™ gas sensors are properly addressed at the 1600/6400 (Section 5.3.2)
and that they match device ID’s on the I/O Module and/or the Modbus™ gas sensors.
Do not have address’s entered for 4-20mA outputs if there are no AO-4 Modules connected.
Ensure that there are no duplications of device # and address # at the 1600/6400 or at the I/O Modules and
Modbus™ gas sensors.

NOTE: Device numbers at the 1600/6400 are in decimal format, while device numbers at the I/O
Modules and the Modbus™ gas sensors are in hexadecimal format.


For more information Contact Detcon’s Technical Service by phone at 281-367-4100, or by e-mail at

[email protected]

.



10.0 Spare Parts


975-041400-000

RL-4 Relay Module (As applicable)

976-041400-000

DA-4 4-20mA Input Module (As applicable)

975-041401-000

AO-4 4-20mA Output Module (As applicable)

975-041402-000

DI-4 Contact Input Module (As applicable)

360-15DCF6-000

DC Power Filter

360-SWS150-024

24VDC Power Supply

320-283934-700

VAC (230VAC) Over Voltage Module

320-283931-800

VDC (24VAC) Over Voltage Module

500-003052-100

1600 Main Controller Assembly with LCD

500-003052-400

6400 Main Controller Assembly with LCD

500-003053-001

Optional RS-232 Serial Communications Module PCB

976-485485-000

RS-485 Isolated Repeater

This manual is related to the following products: