4 touch screen utilities, 5 dipswitch settings, 0 program menu protection – Detcon 6400-N4X User Manual
Page 24: Touch screen utilities, Dipswitch settings, Program menu protection, Figure 28 screen utilities

1600/6400-N4X
1600/6400-N4X- Instruction Manual
Rev. 1.1
Page 20 of 38
5.4 Touch Screen Utilities
This menu item is provided for field adjustment of the LCD screen contrast and provides the means to readjust
calibration of the graphic touch screen should this become necessary. The Touch Screen Utilities key is
located at the bottom center of the Program Menu Screen (Figure 15) and is accessed by pressing the touch
key. Adjust the screen contrast using the up and down arrows. When the screen contrast is satisfactory
(Figure 28), press the ‘ENTER’ key to save the settings.
Figure 28 Screen Utilities
To adjust the calibration of the touch screen key alignment, press the ‘TOUCH SCREEN’ key. The 6400
controller will take the user through a series of prompts to execute calibration. Touch the center of each target
for best results. When calibration is complete press the ‘OK’ key and then press the ‘ENTER’ key to save the
settings.
The Touch Screen can be set up to have the backlight on continuously by placing dipswitch 6 in the ‘OFF’
position (Refer to Figure 28). The unit must be reset to acknowledge any changes in the dipswitch settings.
Note that having the backlight on continuously will shorten the life expectancy of the Touch Screen Display.
5.5 Dipswitch
Settings
The dipswitches are located on the back of the Controller PCB (Figure 30).
1.
ON = Program Menu Access ON, OFF = Program Menu Access OFF
2.
ON = Non-Latching for No Comm Relay, OFF = Latching for No Comm Relay
3.
Reserved (Leave in ON position)
4.
ON = Disable Secondary RS-485 Port, OFF = Enable Secondary RS-485 Port
5.
Reserved (Set at Factory)
6.
ON = Backlight active during operator use, OFF Backlight on at all times
7.
Reserved (Set at Factory)
8.
ON = Enable pushbutton Reset, OFF = Disable pushbutton Reset
6.0 Program
Menu
Protection
A simple form of Program Menu protection is provided to the end-user. On the backside of the controller
module there is an 8 pin dip switch bank. With dipswitch #1 set to the ON position, Program Menu protection
is disabled. In this case, full access to the Program Menu is available to anyone. To set Program Menu
protection, dipswitch #1 is placed in the OFF position. With Program Menu protection enabled, the Main
Menu screen will no longer display the Program Menu key. In its place, an Alarm History key will be shown