1600/6400-N4X

1600/6400-N4X- Instruction Manual

Rev. 1.1

Page 19 of 38

Figure 26 Set-up 4-20mA Outputs


For example, assume setting up two AO-4 modules. Make sure to set each AO-4 module to a unique ID#
using the front panel switches. If Device #’s 1 through 4 are already being used for DA-4 and RL-4 modules,
then set these two AO-4 modules to 5 and 6. The entered values should then look like this:

CH#

Device

Address

01

05

01

02

05

02

03

05

03

04

05

04

05

06

01

06

06

02

07

06

03

08

06

04

5.3.9 View

Channel

History


View Channel History controls all of the logged history of gas readings for each active channel. Select the
channel number of interest and use the scroll arrows to review that channels data. The history log includes the
Date/Time, Time-Weighted-Average (TWA), and the Peak Reading for each hour of operation. When the
memory buffer is full, the oldest data is replaced. The log can retain data for at least 30 days before the buffer
is full and the oldest data is replaced.

Figure 27 View Channel History