Troubleshooting guide – Detcon SmartWireless CX User Manual
Page 25

Sentinel CX
Sentinel CX Sensor Station IM
Rev. 1.4
Page 21 of 26
6. Troubleshooting Guide
Sensor COMM Error
Verify all SmartWireless® CXT devices have a unique Modbus ID number.
Verify the Sensor Input PCA and Relay PCA Modbus address are set correctly
Verify the Radio Module Modbus address is set correctly
Sensor Fault
Verify if sensor displays any fault. If so, follow sensor trouble shooting notes.
Verify if sensor cell needs replacement.
Low Battery
Attach external battery charger
Verify solar panel (if used) is oriented correctly
Poor Link Quality
Verify antenna is securely attached to all devices.
Verify obstructions are eliminated or minimized between SmartWireless® CXT devices and
controller or other CXT devices.
Slow Gas Response
Some delay in gas response is normal if the network update rate is greater than zero. To increase
response time, reduce the update rate. Reducing the update rate will reduce the battery life for
devices.
SmartWireless® CXT not found during controller Auto Configure
Verify CXT device set to correct RF Channel
Verify Radio Module has correct Modbus address
Verify the Sensor Input PCA and Relay PCA Modbus address are set correctly
Verify a proper mA load is present on sensor input. Sensor inputs are not detected unless the mA
input is greater than 1.9mA.
Contact the Detcon Service Department for further troubleshooting assistance at 713-559-9200