beautypg.com

4 4-20ma a & b – Detcon RXT-320 User Manual

Page 18

background image

RXT-320 Wireless Modbus

RXT-320 Wireless IM

Rev. 2.1

Page 14 of 27

provide a complete solution to connecting an RXT-320 to power and providing high-current relay closures.
When using interposing relays, it is strongly recommended to install a transient protection diode (1N4001)
across the relay coil to mitigate the voltage spike when the coil is de-energized.

49.9K

RXT-320

Relay
Coil

Alarm Output

V+

1N4001

Diode

MOSFET N-CH

50V 300mA

From RXT-320
Processor Output

Interposing Relay

Figure 12 Internal Alarm Output Circuit

NOTE: External relays used with this circuit must not exceed voltage/current requirements
and must have transient protection to minimize the voltage spike when the coil is de-energized.

2.3.4

4-20mA A & B

The RXT-320 supports up to two 4-20mA signal inputs (A and B) used for monitoring 4-20mA devices (See
Figure 13). For the primary 4-20mA signal input, use A (green wire). For the secondary 4-20mA signal input,
use B (yellow wire). The input values are continuously read and stored in two separate registers accessible
through Modbus™ at the address assigned to the transceiver. Readings on a 4-20mA input are converted to
representative values, for example, 4mA is read as a value of 400 and 20mA is read as a value of 2000. These
inputs present a load of 162 ohms to ground so a current of 20mA will develop around 3.4V across the input
and ground. This will consume a third less power versus the 250 ohm load used in other implementations.
The inputs are protected for voltages up to 30V but the input reading will reach a maximum of 2048 for
currents greater than 20mA. Electrically the 4-20mA interface supports 2-wire and 3-wire devices.

Figure 13 Up to two Sensors using two 4-20mA Interfaces