network, or Modbus™ (Figure 2). RS-485 serial communication is used for multipoint communications and is
a popular choice due to ease of wiring installation.

Advantages of using RS-485 serial communication

:


¾ Inexpensive method allowing multiple devices to communicate over a single twisted pair of wires.
¾ More data/information can be sent beyond the simple 4-20mA signal.
¾ Transceiver communication up to 4,000 feet without using repeaters.
¾ Highly resistant to induced noise when proper cable and terminations are used.
¾ Two-way (bi-directional), half-duplex, data bus communication consisting of multiple transmitter and

receiver combinations.


Most systems use the RS-485 master/slave architecture for multiple device communication. Each slave unit
has a unique address and responds to data packets generated by the master. The master periodically polls all
connected slave units.

The protocol used by Detcon for the RS-485 communications is the Modbus

¥ RTU, which is compatible with

most PLC’s, MMI’s, and distributed control systems. The Modbus

¥ RTU protocol is standard and allows for

a maximum of 32 sensors and/or field devices to be used in this configuration.

ON / OFF

NO COMM

POWER

ALARM 1

ALARM 3

ALARM 2

FAULT

Typical Sensors

1 2

31 32

Figure 2 RS-485 Network Configuration