Appendix, Specifications, 1 specifications – Detcon FP-700 User Manual
Page 40
Model FP-700
FP-700 Instruction Manual
Rev. 3.0
Page 36 of 40
9. Appendix
9.1 Specifications
Sensor Type:
Continuous diffusion/adsorption type
Matched-Pair Catalytic Bead type
True plug-in replaceable type
Sensor Life:
3-5 years typical
Measuring Ranges:
0-100% LEL (Lower Explosion Limit)
Accuracy/ Repeatability:
±3% 0-50% LEL; ±5% 50-100% LEL
Response/Clearing Time:
T50 < 10 seconds, T90 < 30 seconds
Zero Drift:
<5% per year
Outputs:
Linear 4-20mA DC
RS-485 Modbus™ RTU
Electrical Classification:
Explosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°Cto +75°C)
Class I, Zone 1, Group IIB+H2
ATEX
EEx d IIB+H2 T4 (Tamb = -40°Cto +75°C)
Ingress Protection:
NEMA 4X, IP66
Safety Approvals:
C
CSA
US
Performance to ISA12.13.01-2000 and CSA22.2 #152
ATEX
CE Marking
SIL2 Certi
fi
ed to IEC 61508
Warranty:
Plug-in detector – 2 years
Transmitter – 2 years
Environmental Specifications
Operating Temperature:
-40°F to +167F°; -40°C to +75°C
Storage Temperature:
-40°F to +167F°; -40°C to +75°C
Operating Humidity:
0-99% RH (Non-condensing)
Mechanical Specifications
Dimensions:
7"H x 2.2" Dia.; 178mmH x 65mm Dia. (sensor assembly only)