Operator interface, Figure 13 magnetic programming switches, Figure 13 – Detcon FP-700 User Manual
Page 17: 2 operator interface
![background image](/manuals/366695/17/background.png)
Model FP-700
FP-700 Instruction Manual
Rev. 3.0
Page 13 of 40
Program Switch #1
LED Display
Program Switch #2
MODEL
FP-700
detcon inc.
LEL Sensor
Figure 13 Magnetic Programming Switches
NOTE: While in the Program Mode, if there is no magnetic switch interaction after 4
consecutive menu scrolls, the sensor will automatically revert to normal operating condition.
While changing values inside menu items, if there is no magnet activity after 3-4 seconds
the sensor will revert to the menu scroll.
(Exception to this is with “Signal Output Check” mode.)
3.2 Operator Interface
The operating interface is menu-driven via the two magnetic program switches located under the target marks
of the sensor housing. The two switches are referred to as “PGM1” and “PGM2”. The menu list consists of
three major items that include sub-menus as indicated below. (Refer to the complete Software Flow Chart.)
Normal Operation
Current Reading and Fault Status
Calibration Mode
AutoZero
AutoSpan
Program Mode
View Sensor Status
Sensor Model Type
Current Software Version
Range of Detection
Serial ID address
AutoSpan Level
Days From Last AutoSpan
Remaining Sensor Life
Sensor Bridge Current